2000.35.031

ATEX Head Mount Thermocouple Data Logger
  • Features
    • ATEX Approved
    • Isolated
    • Thermocouple Input
    • RTD Input
    • Loop Powered
    • Near Field Configuration
    • Data Logger



ATEX Head Mount Thermocouple Data Logger

Head mount RTD data logger infographics

The 2000.35.031 is an ATEX approved isolated head mounted thermocouple and RTD temperature transmitter that is isolated up to 1000 Vac between the input and output. The 2000.35.031 has the added ability to store a temperature measurement which can be downloaded to a smart phone. Readings can be stored anywhere between once a second or up to every one hour. The thermocouple datalogger can be set up with a PC, Android phone and with the use of a bluetooth programmer, an iPhone.
The head mounted Thermocouple and RTD temperature transmitter accepts inputs from most standard thermocouples and standard RTD's and provides a 4-20mA output from 6 - 32 Vdc.


2000.35.031 Specifications

Power Supply 6 - 32 Vdc.
ATEX Markings II 1 G Ex ia IIC T3..T6 Ga (Tamb = -40 +55/60/85 °C
II 1 D Ex ia IIIC T85..200°C Da
I M1 Ex ia I T150°C Ma
Thermocouple Input K, S, R, J, T, N, B, E type thermocouples
mV Input -10 to 70 mV
RTD Input Pt100, PT1000, Ni100. 2 Wire, 3 Wire and 4 Wire.
Isolation 1000Vac.
Operative Temperature -40°F +185°F 40°C +85°C
Humidity (non condensing) 30-90%.
Housing Nylon PA66.
Dimensions D x H 1.77 x 0.91inch, 45 x 23mm.
Weight 1 oz 30 g.
EMC For industrial environments.
Immunity EN 61000-6-2.
Emission EN 61000-6-4.
Configuration NFC with PC Configurable, MyPixsys App with Android or iPhone with the blue tooth programmer.

Thermocouple Wiring Connections

Thermocouple Connection
Power Supply 6-32V DC
Postive +Vdc
Negative Out mA
Input 2 wire
Positive Terminal 4
Negative Terminal 3

Thermocouple Input

Head mount thermocouple data logger wiring diagram

2 Wire RTD Wiring Connections

2 Wire Connection
Power Supply 6-32V DC
Postive +Vdc
Negative Out mA
Input 2 wire
White wire Terminal A
Red wire Terminal B

2 Wire RTD Input

Head mount 2 wire RTD data logger wiring diagram

3 Wire RTD Wiring Connections

3 Wire Connection
Power Supply 6-32V DC
Postive +Vdc
Negative Out mA
Input 3 wire
White wire Terminal A
Red wire Terminal B
Red wire Terminal B1

3 Wire RTD Input

Head mount 3 Wire RTD data logger wiring diagram

4 Wire Wiring Connections

4 Wire Connection
Power Supply 6-32V DC
Postive +Vdc
Negative Out mA
Input 4 wire
White wire Terminal A
Red wire Terminal B
White wire Terminal A1
Red wire Terminal B1

4 Wire RTD Input

Head mount 4 Wire RTD data logger wiring diagram

Pixsys Electronics USA