The ATR264 is a versatile programmer specifically designed for the automation of small industrial ovens, laboratory ovens, dryers, and heat treatment systems. It excels in managing process cycles and profiles, offering precise time-based control of variables. With the capability to handle up to 15 user-configurable cycles, each comprising 30 segments for ramp, soak, and cooling stages, the ATR264 ensures that even complex processes can be easily programmed and executed.
Input | °F | °C |
K type Thermocouple | -436 to 2480°F | -260 to 1360°C |
S type Thermocouple | -40 to 3200°F | -20 to 1760°C |
R type Thermocouple | -40 to 3200°F | -20 to 1760°C |
J type Thermocouple | -328 to 2192°F | -200 to 1200°C |
T type Thermocouple | -436 to 752°F | -260 to 400°C |
E type Thermocouple | -436 to 1796°F | -260 to 980°C |
N type Thermocouple | -436 to 2336°F | -260 to 1280°C |
B type Thermocouple | 100 to 3308°F | 100 to 1820°C |
RTD PT100 | -328 to 1112°F | -200 to 600°C |
RTD PT500 | -328 to 284°F | -200 to 140°C |
RTD PT1000 | -328 to 284°F | -200 to 140°C |
NI 100 | -76 to 356°F | -60 to 180°C |
NI 120 | -76 to 464°F | -60 to 240°C |
NTC 10K Ohm Thermistor B3435K | -40 to 257°F | -40 to 125°C |
NTC 10K Ohm Thermistor B3694K | -40 to 302°F | -40 to 150°C |
NTC 2252 Thermistor B3976K | -40 to 302°F | -40 to 150°C |
PTC 1K Ohm Thermistor | -40 to 302°F | -40 to 150°C |
Voltage | 0 to 1V | 0 to 5V |
Voltage | 0 to 10V | 0 to 60mV |
Current | 0 to 20mA | 4 to 20mA |
Potentiometer | 1 to 150 kOhm | |
Digital Input | 2 | PNP |
Output | ||
Analog Outputs: | Configurable 4-20 mA or 0-10 V DC | Control or retransmission |
Relay Outputs: | Up to five relay outputs | 5 A for 250 V AC resistive loads |
Digital Outputs: | 2 Solid State Relay | 12/24, 30 mA |
Output | Upto 5 relays 5 Amp 250 VAC | 2 SSR 12/24, 25 mA |
Communication | ATR264-12ABC-T | Modbus RTU RS485 |
Power Supply | ||
Power Supply | 24 to 230Vac/Vdc. | |
Power Consumption | 8 to 12 W. |
Housing and Environmental | ||
Temperature Rating | Operative- 32°F +113°F -0°C +45°C | |
Humidity | (non condensing) 35-95%. | |
Housing | Polycarbonate UL94V2 self-extinguishing | |
Sealing: | IP65 for the front panel. | IP20 for the box and terminal blocks. |
Dimensions | 1.88 " x 1.88 " x 3.2", | 48 x 48 x 80 mm. |
Weight | 6 oz 185 g. | |
EMC | For industrial environments. | |
Immunity: EN 61000-6-2. | ||
Emission: EN 61000-6-4. | ||
Configuration | My Pixsys APP | Micro USB for programming via PC |
Power supply | ATR264-13ABC | ATR264-12ABC-T |
Positive | Terminal 1 | Terminal 1 |
Negative | Terminal 2 | Terminal 2 |
Output | ||
Relay 1 | ||
Common | Terminal 5 | Terminal 5 |
Normally Open | Terminal 3 | Terminal 3 |
Normally Closed | Terminal 4 | Terminal 4 |
Relay 2 | ||
Common | Terminal 8 | Terminal 8 |
Normally Open | Terminal 6 | Terminal 6 |
Normally Closed | Terminal 7 | Terminal 7 |
Relay 3 | ||
Common | Terminal 8 | |
Normally Open | Terminal 9 | |
Relay 4 | ||
Common | Terminal 8 | |
Normally Open | Terminal 10 | |
SSR Output | Negative 18 | Negative 18 |
Positive 17 | Positive 17 | |
Sensor Input | ||
Thermocouples | Positive 11 | Positive 11 |
Negative 12 | Negative 12 | |
Volts and mA | Positive 11 | Positive 11 |
Negative 12 | Negative 12 | |
RTD Pt100 | Terminal 12 | Terminal 12 |
Common 13 | Common 13 | |
Common 11 | Common 11 | |
Potentiometer | Terminal 15 | Terminal 15 |
Terminal 16 | Terminal 16 | |
Digital input | Terminal 19 | |
Terminal 20 | ||
RS485 | Positive 19 | |
Negative 20 |